♦ ControlLogix Platform

User Manual

IEC 60870-5-101 Slave Communication Module

Page 144 of 193

ProSoft Technology, Inc.

August 2, 2011

And if the parameter offsets are configured as follows:

It would imply that the parameter points would be configured as follows:

M_ME_NA

Monitored Measured Normalized Point

Associated Parameter Point

400 2400

401 2401

402 2402

403 2403

404 2404

So, in order to send change the deadband for the M_ME_NA point 400, the
Master would send a command type 110 to point 2400: