Reference

IEC 60870-5-101 Slave Communication Module

User Manual

ProSoft Technology, Inc.

Page 137 of 193

August 2, 2011

C_SE_NA and C_SE_NB
The Control Normalized Value Set Point Command information object and the
Control Scaled Value Set Point Command information object use one word with
word addressing. For example, if you configured the following information
objects:

The following table describes how these information objects would be used.

Inf. Object Address

Module Database Address

1100

Word 2000 (Word address 2000)

400

Word 10 (Word address 10. Must match the
configuration of point 400 in M_ME_NA.)

1101

Word 2001 (Word address 2001)

401

Word 12 (Word address 12. Must match the
configuration of point 401 in M_ME_NA.)

1102

Word 2002 (Word address 2002)

402

Word 18 (Word address 18. Must match the
configuration of point 402 in M_ME_NA.)