MVI56-101S ♦ ControlLogix Platform

User Manual

IEC 60870-5-101 Slave Communication Module

Page 48 of 193

ProSoft Technology, Inc.

August 2, 2011

2.3.26 Time Type

[0] = None, [1] = CP24, or [2] = CP56

Separate parameters exist for multiple ASDUs. This parameter defines the time
format used with data events.

2.3.27 Use Balanced Mode

Y

-

Y

ES

or N

-

N

O

This parameter specifies if the port will use balanced mode. If balanced mode is
used, only one controlled station will be permitted on the port. If unbalanced
mode is used, multiple controlled stations can be used on a port.

Refer to module Initialization (page Error! Bookmark not defined.) for more
information on these modes.

2.3.28 Retry Count

0 to 255

In balanced mode, this parameter specifies the number of retries (0 to 255) if a
response is not received. In unbalanced mode, this parameter is ignored.