MVI56-101S ♦ ControlLogix Platform

User Manual

IEC 60870-5-101 Slave Communication Module

Page 38 of 193

ProSoft Technology, Inc.

August 2, 2011

2.3

[IEC-870-5-101 Port 0]

This section provides information required to configure a slave application with
the module.

2.3.1 Enabled

Y

ES

or N

O

Enables or disables the primary port. If the port is not enabled (No), then the
module will not use the port. If the port is enabled (Yes), the module will emulate
an IEC 60870-101 slave device on the port.

2.3.2 Time DB Offset

-1, or 0

to 3994

This parameter defines the location in the database where the time maintained
for the IEC protocol is copied. This time is updated whenever a time
synchronization command is received from the host and continually as the
program runs. If the parameter is set to -1, the time will not be placed in the
database.