ProSoft Technology MVI56-101S User Manual

Page 67

Advertising
background image

MVI56-101S ♦ ControlLogix Platform

Configuring the MVI56-101S Module

IEC 60870-5-101 Slave Communication Module

User Manual

ProSoft Technology, Inc.

Page 67 of 193

August 2, 2011

2.18 [C_SE_NB_1]

This section defines the scaled setpoint database. This information is sourced
from the remote Master and is transferred to the database.

You can associate a command with a monitored single-point database value to
coordinate the command/monitor operation. You must enter the correct M

ONITOR

P

OINT

# and M

ONITOR

DB

ADDRESS

values in the table. If the R

EQUIRE

S

ELECT

parameter is not set to zero, a select command must be received before an
execute command will be processed.

This section takes the following parameters:
P

OINT

#

DB

ADDRESS

M

ONITOR

P

OINT

#

M

ONITOR

DB

ADDRESS

R

EQUIRE

S

ELECT

Each point consumes one word. The DB

A

DDRESS

value corresponds to the word

offset in the database.

The

DB

ADDRESS

should be located in a database area that is being constantly

moved from the Master to the module.

For additional information on how to set these parameters, see the Reference
chapter of this manual.

Advertising
This manual is related to the following products: