2.3.35 Receive Timeout

0 to 65535

milliseconds

This parameter specifies the minimum number of milliseconds to wait after the
first byte of a frame is received before a timeout condition is set. Be careful not to
set this parameter too small. If the timeout condition is set, all bytes in the frame
received will be discarded.

2.3.36 Hardware Handshaking

N

ONE

, RTS/CTS,

DTR/DSR, M

ODEM

Selects the hardware handshaking type. RTS/CTS, DTR/DSR and M

ODEM

options are most commonly used for older telephone line modems. RTS/CTS
and DTR/DSR are also commonly used with leased-line data modems. The
M

ODEM

option is also commonly used with dial-up modems. When the messages

must go out if the modem is not connected, the module will assert the DTR line
which will cause the modem to dial the number in the modem’s configuration.
The module does not have the functionality to dial the number to be called for the
modem. The module reconnects after 30 seconds of inactivity.