Reference MVI56-101S

♦ ControlLogix Platform

User Manual

IEC 60870-5-101 Slave Communication Module

Page 136 of 193

ProSoft Technology, Inc.

August 2, 2011

C_BO_NA
A Control 32-Bit Bitstring Command information object occupies two words and
uses double-word addressing.

For example, if you configured the following information objects:

These information objects would be used as follows:

Inf. Object Address

Module Database Address

3100

Words 3000 and 3001 (Double-word address 1500)

600

Words 2000 and 2001(Double-word address 1000. Must
match the configuration of point 600 in M_BO_NA.)

3101

Words 3002 and 3003 (Double-word address 1501)

601

Words 2002 and 2001 (Double-word address 1001. Must
match the configuration of point 601 in M_BO_NA.)

3102

Words 3003 and 3004 (Double-word address 1502)

602

Words 2004 and 2005 (Double-word address 1002. Must
match the configuration of point 602 in M_BO_NA.)