3.1

Module Data Object (ModuleDef870)

All data related to the MVI56-101S module is stored in a user defined data type.
An instance of the data type is required before the module can be used. This is
done by declaring a variable of the data type in the Controller Tags Edit Tags
dialog box.

The following table describes the structure of this object.

Name Data

Type

Description

InStat InStat870

Status

information in each read block

ReadData

INT[600]

Data read from module

WriteData

INT[600]

Data to write to module

BP

Backplane870S

Data to handle backplane logic

ReadClock Clock870

WriteClock Clock870

CommandBits CommandsBits870S

PassEvents Event870[10]

EventCount INT

This object contains objects that define user and status data related to the
module. Each of these object types is discussed in the following topics of the
document.

3.1.1 Status Object (InStat870)

This object views the status of the module. The InStat870 object shown below is
updated each time a read block is received by the processor. Use this data to
monitor the state of the module at a "real-time rate".

Name Data

Type

Description

PassCnt

INT

Program cycle counter for module

Product

INT[2]

Product code for module

Rev

INT[2]

Revision level of module’s code

OP

INT[2]

Operating system version for module

Run

INT[2]

Run number for module

BlkErrs BlkStat870

Data

block transfer statistics

Read

INT

Total number of blocks read by the module

Write

INT

Total number of blocks written by the module

Parse

INT

Total number of blocks parsed by the module

Err

INT

Total number of block transfer errors

Port_Select

INT

Current port on module being utilized

Bad_CRC

INT

Total number of frames with bad CRC errors

Sync_Err

INT

Total number of sync errors

Len_Err

INT

Total number length errors

Timeouts

INT

Total number timeout errors

RX_Frames

INT

Total number RX frames

TX_Frames

INT

Total number TX frames

Refer to the Reference chapter for a complete listing of the data stored in this
object.