MVI56-101S ♦ ControlLogix Platform

Configuring the MVI56-101S Module

IEC 60870-5-101 Slave Communication Module

User Manual

ProSoft Technology, Inc.

Page 49 of 193

August 2, 2011

2.3.29 Response Timeout

0 to 65535

milliseconds

This parameter specifies the minimum number of milliseconds to wait for a
response to a primary message. Do not set this parameter too small or timeout
conditions may prevent successful data transmission. If the timeout is
recognized, the message will be retransmitted up to the number of times
specified in the Retry Count parameter. This parameter is only used in balance
mode.

2.3.30 Baud Rate

300, 600, 1200, 2400, 4800, 9600, 19200, or 38400

This parameter specifies the baud rate for the primary port on the module. Baud
rates from 300 to 38400 are supported on the module.

2.3.31 Parity

None, Odd, Even

Parity is a simple error checking algorithm used in serial communication. This
parameter specifies the type of parity checking to use.

All devices communicating through this port must use the same parity setting.

2.3.32 RTS On

0 to 65535

milliseconds

This parameter sets the number of milliseconds to delay after Ready To Send
(RTS) is asserted before data will be transmitted.

2.3.33 RTS Off

0 to 65535 milliseconds

This parameter sets the number of milliseconds to delay after the last byte of
data is sent before the RTS modem signal will be set low.

2.3.34 Minimum Delay

0 to 65535

milliseconds

This parameter defines the minimum number of milliseconds to wait before a
response is sent from the unit.