ProSoft Technology MVI56-101S User Manual

Page 128

Advertising
background image

Reference MVI56-101S

♦ ControlLogix Platform

User Manual

IEC 60870-5-101 Slave Communication Module

Page 128 of 193

ProSoft Technology, Inc.

August 2, 2011

M_ME_NA and M_ME_NB

A Monitor Normalized Measured information object or Monitor Scaled Measured
information object occupies one word and uses word addressing.

For example, if you configured the following information objects:

The following table describes how these information objects would be stored in
the module.

Inf. Object Address

Module Database Address

400

Word 10 (Word address 10)

401

Word 12 (Word address 12)

402

Word 18 (Word address 18)

Monitor Normalized Measured information objects use a data representation
defined by the protocol specification to represent fractional decimal values. The
following table describes the value for each bit as a reciprocal power of two (2),
that is two (2) raised to the power of a negative exponent (-1 through -15). Bit 15
is the Sign Bit.

Bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Value
Hex(h)
Decimal

Sign

4000h
2

-1

2000h
2

-2

1000h
2

-3

800
h
2

-4

400
h
2

-5

200
h
2

-6

100
h
2

-7

80
h
2

-8

40
h
2

-9

20
h
2

-10

10
h
2

-11

8h
2

-12

4h
2

-13

2h
2

-14

1h
2

-15

4000h
0.5

0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0

2000h
0.25

0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0

1000h
0.125

0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0

6000h
0.75

0 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0

3210h
0.395751953125

0 0 1 1 0 0 1 0 0 0 0 1 0 0 0 0

Advertising
This manual is related to the following products: