MVI56-101S ♦ ControlLogix Platform

Configuring the MVI56-101S Module

IEC 60870-5-101 Slave Communication Module

User Manual

ProSoft Technology, Inc.

Page 39 of 193

August 2, 2011

2.3.3 Disable Time Sync Events

Y

ES

or

N

O

This feature can be used when the Master receives the event timestamp with
only minutes and milliseconds information for each event message (CP24 time
type). If the parameter is set to N, the spontaneous time sync events will be
generated to indicate the change of hour. If this parameter is set to Y, then the
spontaneous time sync event messages are not generated to indicate the
change of hour.

2.3.4 Data Link Address Value

0 to

65535

This parameter defines the Data Link Address for the emulated device on the
module. This address identifies the module on the network along with the
common address of ASDU.

2.3.5 Data link address length

0, 1, or 2

This parameter specifies the number of octets used for the data link address.
This parameter must be set the same for all devices on the network. A value of 0
is only valid when the balanced mode is used. If unbalanced mode is used, a
value of 1 or 2 must be used.

2.3.6 Common Address of ASDU Val

0

to 65535

This parameter specifies the common address of the ASDU (section address) for
access to data in the module. There is only one value entered for access to all
data in the module.

Refer to ASDU Configuration for more information on Application Service Data
Unit configuration.

2.3.7 Common Address of ASDU Len

1 or 2

This parameter specifies the number of octets used for the common address of
ASDU. This parameter must be set the same for all devices on the network.

2.3.8 Inform. Object Address Len

1, 2, or 3

This parameter specifies the number of octets used to define the address of an
information object (point address).