Reference MVI56-101S

♦ ControlLogix Platform

User Manual

IEC 60870-5-101 Slave Communication Module

Page 120 of 193

ProSoft Technology, Inc.

August 2, 2011

Balanced Mode

During balanced mode, the link must be initialized in both directions. The MVI56-
101S module also always reinitializes the link after it receives an initialization
request from the Master. Therefore, the following initialization occurs during
balanced mode, after MVI56-101S boots.

Master

101

Slave

Master initializes

the link

101S driver

initializes the link

101S driver

reinitializes the

link

Status of Link

Status of Link Response

Reset Remote Link

ACK

Status of Link

Status of Link Response

Reset Remote Link

ACK

Status of Link

Status of Link Response

Reset Remote Link

ACK

After the initialization procedure is completed, the Master and the MVI56-101S
start communicating. During communication, if the Master fails to respond to a
message from the module, the module will retry for a configured number of times.
If the Master still fails to respond, the module will attempt to initialize the line
again.