ProSoft Technology MVI56-101S User Manual

Page 75

Advertising
background image

MVI56-101S ♦ ControlLogix Platform

Ladder Logic

IEC 60870-5-101 Slave Communication Module

User Manual

ProSoft Technology, Inc.

Page 75 of 193

August 2, 2011

3 Enter the Name, Description and Slot options for your application. You must

select the Comm Format as D

ATA

-

INT in the dialog box, otherwise the

module will not communicate. Click OK to continue.

Parameter Value

Name

Enter a module identification string. Example: 101S_2

Description

Enter a description for the module. Example: IEC

60870-

5-101

S

LAVE

C

OMMUNICATION

M

ODULE

Comm Format

Select D

ATA

-INT.

Slot

Enter the slot number in the rack where the MVI56-101S
module is located.

Input Assembly Instance

1

Input Size

250

Output Assembly Instance

2

Output Size

248

Configuration Assembly Instance

4

Configuration Size

0

4 Select the Requested Packet Interval value for scanning the I/O on the

module. This value represents the minimum frequency that the module will
handle scheduled events. This value should not be set to less than 1
millisecond. The default value is 5 milliseconds. Values between 1 and 10
milliseconds should work with most applications.