ProSoft Technology MVI56-101S User Manual

Page 130

Advertising
background image

Reference MVI56-101S

♦ ControlLogix Platform

User Manual

IEC 60870-5-101 Slave Communication Module

Page 130 of 193

ProSoft Technology, Inc.

August 2, 2011

5.3.5 Using

Control

(Command) Information Objects

The MVI56-101S module supports the following Control information objects:

ASDU Type

Information Object Description

C_SC_NA Control

Single

Command

C_DC_NA

Control Double Command

C_RC_NA

Control Regulating Step Command

C_BO_NA

Control 32-Bit Bitstring Command

C_SE_NA

Control Normalized Value Set Point Command

C_SE_NB Control

Scaled

Value Set Point Command

C_SE_NC

Control Short Floating-Point Value Set Point Command

Each Control information object is identified by its Information Object Address.
For each Control information object, configure the following parameters:

Point # - This is the Information Object Address of the information object. It
identifies the information object in the network. This address must be unique for
each Common ASDU Address in the network.

DB Address - This is the database location in the MVI56-101S module
associated with the information object.

Monitor Point # - This is the Information Object Address of the associated
Monitor information object to be sent to the Client once the Control request is
received.

Monitor DB Address - The user might (optionally) configure a Monitor information
object to be sent by the MVI56-101S module when it receives the command for
that specific information object.

Require Select - This parameter configures the information object to require a
Select request before the Operate command.

Example (C_SC_NA)