ProSoft Technology MVI56-101S User Manual

Page 60

Advertising
background image

Configuring the MVI56-101S Module

MVI56-101S ♦ ControlLogix Platform

User Manual

IEC 60870-5-101 Slave Communication Module

Page 60 of 193

ProSoft Technology, Inc.

August 2, 2011

2.11 [M_ME_NC_1]

This section defines the monitored short-float point database. This information is
sourced from the database and is transferred to the remote Master unit.

To determine the IOA (Information Object Address) for each object, add the
P

OINT

#

in the following section to the value of the M_ME_NC Parameter Offset

parameter set in the previous section.

This section takes the following parameters:
P

OINT

#

DB

ADDRESS

G

ROUPS

D

EFAULT

D

EADBAND

IV

DB

B

IT

Each point consumes four 8-bit bytes (two 16-bit words). The DB

A

DDRESS

value

corresponds to the double-word offset address in the database.

The DB

ADDRESS

should be located in a database area that is being constantly

moved from the module to the Master.

For additional information on how to set these parameters, see the Reference
chapter of this manual.