MVI56-101S ♦ ControlLogix Platform

Reference

IEC 60870-5-101 Slave Communication Module

User Manual

ProSoft Technology, Inc.

Page 127 of 193

August 2, 2011

M_BO_NA

A Monitored 32-Bit Bitstring Point occupies two words and uses double-word
addressing.

For example, if you configured the following points:

The following table describes how these points would be stored in the module
memory database.

Inf. Object Address

Module Database Address

600

Words 2000 and 2001 (Double-word address 1000)

601

Words 2002 and 2003 (Double-word address 1001)

602

Words 2004 and 2005 (Double-word address 1002)