Configuring the MVI56-101S Module

MVI56-101S ♦ ControlLogix Platform

User Manual

IEC 60870-5-101 Slave Communication Module

Page 68 of 193

ProSoft Technology, Inc.

August 2, 2011

2.19 [C_SE_NC_1]

This section defines the short-float setpoint database. This information is sourced
from the remote Master and is transferred to the database.

You can associate a command with a monitored single-point database value to
coordinate the command/monitor operation. You must enter the correct M

ONITOR

P

OINT

# and M

ONITOR

DB

ADDRESS

values in the table. If the R

EQUIRE

S

ELECT

parameter is not set to zero, a select command must be received before an
execute command will be processed.

This section takes the following parameters:
P

OINT

#

DB

ADDRESS

M

ONITOR

P

OINT

#

M

ONITOR

DB

ADDRESS

R

EQUIRE

S

ELECT

Each point consumes two words. The

DB

A

DDRESS

value corresponds to the

double-word offset in the database.

The

DB

ADDRESS

should be located in a database area that is being constantly

moved from the Master to the module.

For additional information on how to set these parameters, see the Reference
chapter of this manual.