ProSoft Technology MVI56-101S User Manual

Page 135

Advertising
background image

MVI56-101S ♦ ControlLogix Platform

Reference

IEC 60870-5-101 Slave Communication Module

User Manual

ProSoft Technology, Inc.

Page 135 of 193

August 2, 2011

C_RC_NA
A Control Regulating Step Command information object occupies one byte and
uses byte addressing.

For example, if you configured the following information objects:

The following table describes how these information objects would be used.

Inf. Object Address

Module Database Address

1000

Low Byte of word 250 (Byte address 500)

300

Low Byte of word 20 (Byte address 40. Must match
configuration of point 300 in M_ST_NA.)

1001

Low Byte of word 260 (Byte address 520)

301

Low Byte of word 30 (Byte address 60. Must match
configuration of point 301 in M_ST_NA.)

1002

High Byte of word 270 (Byte address 541)

302

High Byte of word 40 (Byte address 81. Must match
configuration of point 302 in M_ST_NA.)