ProSoft Technology MVI46-DFNT User Manual

Page 101

Advertising
background image

MVI46-DFNT ♦ SLC Platform

Reference

EtherNet/IP Client/Server Communication Module

User Manual

ProSoft Technology, Inc.

Page 101 of 177

October 12, 2010

4.6

Error Codes

The module error codes are listed in this section. Error codes returned from the

command list process are stored in the command list error memory region. A

word is allocated for each command in the memory area. The error codes are

formatted in the word as follows: The least-significant byte of the word contains

the extended status code and the most-significant byte contains the status code.
Use the error codes returned for each command in the list to determine the

success or failure of the command. If the command fails, use the error code to

determine the cause of failure.

Note: The Module Specific error codes (not DF1 compliant) are returned from within the module
and never returned from an attached DF1 slave device. These are error codes that are part of the
DF1 protocol or are extended codes unique to this module. The standard DF1 error codes can be
found in the DF1 Protocol and Command Set Reference Manual (Publication 1770-6.5.16) from
Rockwell Automation. The most common errors for the DF1 protocol are shown in the following
tables:

4.6.1 Local STS Error Codes

Code (Int)

Code (Hex) Description

0

0x0000

Success, no error

256

0x0100

DST node is out of buffer space

512

0x0200

Cannot guarantee delivery (Link Layer)

768

0x0300

Duplicate token holder detected

1024

0x0400

Local port is disconnected

1280

0x0500

Application layer timed out waiting for response

1536

0x0600

Duplicate node detected

1792

0x0700

Station is offline

2048

0x0800

Hardware fault