If a configuration error is present for the pass-through port, the configuration error

word contains a value other than zero. The configuration error word bits have the

following definitions:

Bit

Description

Value

0

Invalid enable code

0x0001

1

Invalid local station ID

0x0002

2

Invalid protocol or termination type

0x0004

3

Invalid baud rate

0x0008

4

Invalid parity

0x0010

5

Invalid data bits

0x0020

6

Invalid stop bits

0x0040

7

0x0080

8

Invalid Use CTS Line selection

0x0100

9

Invalid retry count

0x0200

10

0x0400

11

0x0800

12

0x1000

13

0x2000

14

0x4000

15

0x8000


Correct any invalid data in the configuration for proper module operation. When

the configuration contains a valid parameter set, all the bits in the configuration

words are clear. This does not indicate that the configuration is valid for the user

application. Make sure each parameter is set correctly for the specific

application.
If the APP, BP ACT and OK LEDs blink at a rate of every one-second, this

indicates a serious problem with the module. Call ProSoft Technology support to

arrange for repairs.

3.1.1 Ethernet LED Indicators

LED

State

Description

Data

OFF

No activity on the Ethernet port.

GREEN Flash

The Ethernet port is actively transmitting or receiving data.

Link

OFF

No physical network connection is detected. No Ethernet

communication is possible. Check wiring and cables.

GREEN Solid

Physical network connection detected. This LED must be ON

solid for Ethernet communication to be possible.