ProSoft Technology MVI46-DFNT User Manual

Page 83

Advertising
background image

MVI46-DFNT ♦ SLC Platform

Reference

EtherNet/IP Client/Server Communication Module

User Manual

ProSoft Technology, Inc.

Page 83 of 177

October 12, 2010

Disabling the RSLinx Driver for the Com Port on the PC
The communication port driver in RSLinx can occasionally prevent other

applications from using the PC’s COM port. If you are not able to connect to the

module’s configuration/debug port using ProSoft Configuration Builder (PCB),
HyperTerminal or another terminal emulator, follow these steps to disable the
RSLinx Driver.
1 Open RSLinx and go to C

OMMUNICATIONS

>RSW

HO

2 Make sure that you are not actively browsing using the driver that you wish to

stop. The following shows an actively browsed network:

3 Notice how the DF1 driver is opened, and the driver is looking for a processor

on node 1. If the network is being browsed, then you will not be able to stop

this driver. To stop the driver your RSWho screen should look like this:

Branches are displayed or hidden by clicking on the

or the

icons.

4 When you have verified that the driver is not being browsed, go to

C

OMMUNICATIONS

>C

ONFIGURE

D

RIVERS

You may see something like this:

Advertising