Step 5 - (Optional) Configure the Port 3 Pass-Through
After you configure the MVI46-DFNT pass-through server, you may configure
Port 3 to receive DF1 commands in order to allow access from a DF1 Master to
the SLC data file.
In order to accomplish this, refer to the DF1-Pass-Through Port Section at the
MVI46-DFNT configuration file.
4.17.1 Troubleshooting
If you are unable to connect the software converter to the MVI46-DFNT you may
have to configure the communication parameter used in the network. In order to
achieve a functional communication between the local PC and the SLC
processor, all communication parameters at each part of the network must
match. This means that the communication parameters configured at the
following parts of the network should be the same:
SLC processor Channel 0 (Use RSLogix500)
MVI46-DFNT configuration (DF1 Pass-Through Server Port 1)
Serial/IP Software Converter (required, must obtain separately)
RSLinx RS-232 driver (use the auto-config feature)