Reference

MVI46-DFNT ♦ SLC Platform

User Manual

EtherNet/IP Client/Server Communication Module

Page 108 of 177

ProSoft Technology, Inc.

October 12, 2010

[Section]/Item

Value

Range

Description

Busy Timeout:

100 to
65535

milliseconds

This parameter sets the number of milliseconds the
server will wait for the pass-through port to become

available. Valid data range for this parameter is 100 to

65535.

Baud Rate:

1200 to

19200

This is the baud rate to be used on the port. Enter the
baud rate as a value. For example, to select 19K baud,

enter 19200.

Parity:

N, O, E

This is the Parity code to be used for the port. The
coded values are as follows: N=None, O=Odd,

E=Even.

Data Bits:

5 to 8

This parameter sets the number of data bits for each

word used by the protocol.

Stop Bits:

1 or 2

This parameter sets the number of stop bits for each

data value sent.

RTS On:

0 to 65535

This parameter sets the number of milliseconds to

delay after RTS is asserted before the data is

transmitted.

RTS Off:

0 to 65535

This parameter sets the number of milliseconds to
delay after the last byte of data is sent before the RTS

modem signal will be set low.

Use CTS Line:

Y or N

This parameter specifies if the CTS modem control
line is to be used. If the parameter is set to N, the CTS

line will not be monitored. If the parameter is set to Y,

the CTS line is monitored and must be high before the
module sends data. Normally, this parameter is

required when half-duplex modems are used for

communication (2-wire).

[Section]/Item

Value

Range

Description

[DF1 Pass-Through Port]

Start header for the pass-through port

Enabled:

Y or N

This parameter specifies if the pass-through port will be
used. This port should only be used if the DF1 pass-

through server is enabled.

Local Station ID:

0 to 254

This parameter specifies the local station ID for all DF1
messages sent to this port. A value of 255 is not

permitted as this is the broadcast address. The

application only accepts messages with this node

address.

Protocol:

F or H

F=full duplex, H=half-duplex. The value selected

should match that set for the SLC processor.

Termination Type:

B or C

This parameter sets the termination message type for
the DF1 protocol. The value selected should match that

used in the SLC. Valid values are B for BCC and C for

CRC.

Baud Rate:

1200 to

19200

This is the baud rate to be used on the port. Enter the
baud rate as a value. For example, to select 19K baud,

enter 19200.

Parity:

N, O, E

This is the Parity code to be used for the port. The
coded values are as follows: N=None, O=Odd,

E=Even.