ProSoft Technology MVI46-DFNT User Manual
Page 108

Reference
MVI46-DFNT ♦ SLC Platform
User Manual
EtherNet/IP Client/Server Communication Module
Page 108 of 177
ProSoft Technology, Inc.
October 12, 2010
[Section]/Item
Value
Range
Description
Busy Timeout:
100 to
65535
milliseconds
This parameter sets the number of milliseconds the
server will wait for the pass-through port to become
available. Valid data range for this parameter is 100 to
65535.
Baud Rate:
1200 to
19200
This is the baud rate to be used on the port. Enter the
baud rate as a value. For example, to select 19K baud,
enter 19200.
Parity:
N, O, E
This is the Parity code to be used for the port. The
coded values are as follows: N=None, O=Odd,
E=Even.
Data Bits:
5 to 8
This parameter sets the number of data bits for each
word used by the protocol.
Stop Bits:
1 or 2
This parameter sets the number of stop bits for each
data value sent.
RTS On:
0 to 65535
This parameter sets the number of milliseconds to
delay after RTS is asserted before the data is
transmitted.
RTS Off:
0 to 65535
This parameter sets the number of milliseconds to
delay after the last byte of data is sent before the RTS
modem signal will be set low.
Use CTS Line:
Y or N
This parameter specifies if the CTS modem control
line is to be used. If the parameter is set to N, the CTS
line will not be monitored. If the parameter is set to Y,
the CTS line is monitored and must be high before the
module sends data. Normally, this parameter is
required when half-duplex modems are used for
communication (2-wire).
[Section]/Item
Value
Range
Description
[DF1 Pass-Through Port]
Start header for the pass-through port
Enabled:
Y or N
This parameter specifies if the pass-through port will be
used. This port should only be used if the DF1 pass-
through server is enabled.
Local Station ID:
0 to 254
This parameter specifies the local station ID for all DF1
messages sent to this port. A value of 255 is not
permitted as this is the broadcast address. The
application only accepts messages with this node
address.
Protocol:
F or H
F=full duplex, H=half-duplex. The value selected
should match that set for the SLC processor.
Termination Type:
B or C
This parameter sets the termination message type for
the DF1 protocol. The value selected should match that
used in the SLC. Valid values are B for BCC and C for
CRC.
Baud Rate:
1200 to
19200
This is the baud rate to be used on the port. Enter the
baud rate as a value. For example, to select 19K baud,
enter 19200.
Parity:
N, O, E
This is the Parity code to be used for the port. The
coded values are as follows: N=None, O=Odd,
E=Even.