ProSoft Technology MVI46-DFNT User Manual

Page 128

Advertising
background image

Reference

MVI46-DFNT ♦ SLC Platform

User Manual

EtherNet/IP Client/Server Communication Module

Page 128 of 177

ProSoft Technology, Inc.

October 12, 2010

4.12 PLC-5 Processor Specifics

This section contains information specific to the PLC-5 processor with relation to

the DF1 command set. The commands specific to the PLC-5 processor contain a

sub-element code field. This field selects a sub-element field in a complex data

table. For example, to obtain the current accumulated value for a counter or

timer, the sub-element field should be set to 2. The tables below show the sub-

element codes for PLC-5 complex data tables.

4.12.1 PLC-5 Sub-Element Codes

Timer / Counter

Code

Description

0

Control

1

Preset

2

Accumulated

Control

Code

Description

0

Control

1

Length

2

Position

PD*

Code

Description

0

Control

2

SP

4

Kp

6

Ki

8

Kd

26

PV

*All PD values are floating point values, so they are two words long.