ProSoft Technology MVI46-DFNT User Manual
Page 36

Configuring the MVI46-DFNT Module
MVI46-DFNT ♦ SLC Platform
User Manual
EtherNet/IP Client/Server Communication Module
Page 36 of 177
ProSoft Technology, Inc.
October 12, 2010
Parameter
Range
Description
Node IP
Address
xxx.xxx.xxx.xxx
The IP address of the device being addressed by the command.
Slot
When addressing a ControlLogix processor, the slot number corresponds to
the slot in the rack containing the controller being addressed. In the
ControlLogix platform, the controller can be placed in any slot and the rack
may contain multiple processors. This parameter uniquely selects a controller
in the rack.
Use a value of -1 when interfacing to an SLC 5/05 or a
PLC5. These devices do not have a slot number.
Function Code See Command
Function Codes (page
33)
These parameters specify the function to be executed by the command. The
Reference chapter in this manual describes the meaning of these values for
each of the available supported commands. Following is a complete list of the
command supported by the Client driver.
Function Code Listing
Basic Command Set
1
Protected Write
2
Unprotected Read
3
Protected Bit Write
4
Unprotected Bit Write
5
Unprotected Write
PLC-5 Command Set (0x0F)
100
Word Range Write (Binary Address)
101
Word Range Read (Binary Address)
102
Read-Modify-Write (Binary Address)
150
Word Range Write (ASCII Address)
151
Word Range Read (ASCII Address)
152
Read-Modify-Write (ASCII Address)
SLC Command Set (0x0F)
501
Prot Typed Read with 2 addr fields
502
Prot Typed Read with 3 addr fields
509
Prot Typed Write with 2 addr fields
510
Prot Typed Write with 3 addr fields
511
Prot Type Write with Mask 3 addr field
Function
Parameters
See Command
Function Codes (page
33)
The number of auxiliary parameters required depends on the function code
selected for the command.