4.14 MicroLogix Processor Specifics

This section contains information specific to the MicroLogix processor based

family when used with the DF1 command set. The MicroLogix processor

commands support a file type field entered as a single character to denote the

data table to interface with in the command. This field is the same as that used

for a SLC processor. The following table defines the relationship of the file types

accepted by the module and the SLC file types:

4.14.1 SLC File Types

File Type

Description

S

Status

B

Bit

T

Timer

C

Counter

R

Control

N

Integer

F

Floating-point

Z

String

A

ASCII

The File Type Command Code is the ASCII character code value of the File Type

letter. This is the value to enter into the "File Type" parameter of the DF1

Command configurations in the data tables in the ladder logic.
Additionally, the SLC specific functions (502, 510 and 511) support a sub-

element field. This field selects a sub-element field in a complex data table. For

example, to obtain the current accumulated value for a counter or timer, the sub-

element field should be set to 2.