4.11.9 Function Code #150 - Word Range Write (PLC-5 Command)

(ASCII Address)

Column

Parameter

Description

Parameter

1

Enable/Type Word

0=Disabled, 1=Continuous and 2=Conditional.

2

Virtual Database Address

This parameter defines the database address of the first
data point to be associated with the command.

3

Poll Interval

Minimum time in tenths of a second to wait before
polling with this command.

4

Count

Number of data word values to be considered by the
function.

5

Swap Type Code

Swap type code for command: 0=None, 1=Swap words,
2=Swap words & bytes and 3=swap bytes in each word.

6

Node Address

Address of unit to reach on the data highway.

7

Slot Number

Processor slot number in Control/CompactLogix rack.
Use -1 for PLC5 & SLC processors.

8

Function Code = 150

Word Range Write Command.

9

File String

PLC-5 address as specified as an ASCII string. For
example, N10:300.

P1

10 to 12

Not Used

These fields are not used by the command. Values
entered in these columns will be ignored.

P2 to P4


This function writes one or more words of data to a PLC data table. This function

should work on the following devices: PLC-5.