In order to complete the configuration of the MSG instruction, select the S
ETUP
S
CREEN
area of the MSG object. This displays the following dialog box.
Select the C
OMMUNICATION
C
OMMAND
to execute from the following list of
supported commands.
PLC5 Type Read
PLC2 Unprotected Read
PLC5 Typed Read to PLC
PLC Typed Logical Read
The T
ARGET
D
EVICE
D
ATA
T
ABLE
A
DDRESS
must be set to a valid file element
(such as, N11:0) for SLC and PLC5 messages. For the PLC2 Unprotected Read
message, set the address to the database index (such as, 1000) to consider with
the command.
The M
ULTI
H
OP
option must be set to Y
ES
.
The M
ULTI
H
OP
tab portion of the dialog
box must be completed as shown in the following window:
Set the IP address value to the module’s Ethernet IP address. You must press
the "Insert" key to add the second line for ControlLogix Backplane and set the
slot number to zero.