ProSoft Technology MVI46-DFNT User Manual

Page 125

Advertising
background image

MVI46-DFNT ♦ SLC Platform

Reference

EtherNet/IP Client/Server Communication Module

User Manual

ProSoft Technology, Inc.

Page 125 of 177

October 12, 2010

4.11.14 Function Code #509 - Protected Typed Logical Write (Two

Address Fields)

Column

Parameter

Description

Parameter

1

Enable/Type Word

0=Disabled, 1=Continuous and 2=Conditional.

2

Virtual Database Address

This parameter defines the database address of the
first data point to be associated with the command.

3

Poll Interval

Minimum time in tenths of a second to wait before
polling with this command.

4

Count

Number of data word values to be considered by the
function.

5

Swap Type Code

Swap type code for command: 0=None, 1=Swap
words, 2=Swap words & bytes and 3=swap bytes in
each word.

6

Node Address

Address of unit to reach on the data highway.

7

Slot Number

Processor slot number in Control/CompactLogix rack.
Use -1 for PLC5 & SLC processors.

8

Function Code = 509

Logical Write Command

9

File Type

SLC file type letter as used in file name string. Valid
values for the system are N, S, F, A, ….

P1

10

File Number

SLC file number to be associated with the command.

P2

11

Element Number

The parameter defines the element in the file where
write operation will start.

P3

12

Not Used

This field is not used by the command. Values entered
in this column will be ignored.

P4

This function writes one or more words of data to a PLC data table.