Reference

MVI46-DFNT ♦ SLC Platform

User Manual

EtherNet/IP Client/Server Communication Module

Page 76 of 177

ProSoft Technology, Inc.

October 12, 2010

The DFNT module supports server functionality using the reserved ControlNet

service port 0xAF12. Services supported in the module permit client applications

(that is, RSView, ControlLogix processors and RSLinx) to read from and write to

the module’s database. This document discusses the requirements for attaching

to the module using several client applications.
The following illustration shows the relationship of the DFNT module’s

functionality to devices on an Ethernet network:

Server functionality places all data transfer operations outside the module. There

is no configuration required in the module other than setting up the network and

database parameters in the configuration file. Ladder logic in attached

processors use MSG instructions to perform read and write operations on the

module’s internal database.
When RSLinx links a user application to the module, the module’s server

functionality must be used. RSLinx exists on an Ethernet network only as a client

application. It cannot act as a server. User applications can use the DDE/OPC

capabilities built into RSLinx to interface with the data in the DFNT module.

RSView can link directly to the module using drivers supplied by RSLinx.
The internal database of the DFNT module is used as the source (read requests)

and destination (write requests) for requests from remote clients. Access to the

database depends on the MSG command type executed to interface with the

database. The following table defines the relationship of the module’s internal

database to the addresses required in the MSG instructions: