4.15 ControlLogix Processor Specifics
This section contains information specific to the ControlLogix processor when
used with the DF1 command set. The current implementation of the DF1
command set does not use functions that can directly interface with the
ControlLogix Tag Database. In order to interface with this database, the table-
mapping feature provided by RSLogix 5000 must be used. The software permits
the assignment of ControlLogix Tag Arrays to virtual PLC 5 data tables. The
ProSoft module using the PLC 5 command set defined in this document can then
reach this controller data.