ProSoft Technology MVI46-DFNT User Manual
Page 150

Reference
MVI46-DFNT ♦ SLC Platform
User Manual
EtherNet/IP Client/Server Communication Module
Page 150 of 177
ProSoft Technology, Inc.
October 12, 2010
The T
ARGET
D
EVICE
D
ATA
T
ABLE
A
DDRESS
must be set to a valid file element
(such as, N11:0) for SLC and PLC5 messages. For the PLC2 Unprotected Write
message, set the address to the database index (such as, 1000) to consider with
the command.
The M
ULTI
H
OP
option must be set to Y
ES
.
The M
ULTI
H
OP
tab portion of the dialog
box must be completed as shown in the following window:
Set the IP address value to the module’s Ethernet IP address. You must press
the "Insert" key to add the second line for ControlLogix Backplane and set the
slot number to zero.
PLC5 Read Commands
Read commands transfer data to the PLC5 processor from the DFNT module. An
example rung used to execute a read command is shown in the following
diagram: