Fan overheat drive overheat – GE Industrial Solutions AF-300E$ User Manual

Page 107

Advertising
background image

8-12

( 5 ) Drive overheat

O H 1

Is the drive load
too large?

( 6 ) External failure

Fan overheat

Drive overheat

Reduce the load in
the external equip-
ment or decrease the
duty cycle.

Is the alarm function
of externally
connected equip-
ment activating?

Is the connection
between THR and
CM correct?

O H 2

O H 3

Remove
obstructions.

Yes

Yes

Repair the wiring
and/or connections.

There is the
possibility of
drive failure or
noise related
misoperation.
Contact GE Fuji

Are the cooling fans
in the drive operat-
ing?

Is the passage of
the drive cooling air
obstructed?

Is the ambient
temperature within
the specified limit?

Failure in the drive
or noise related
misoperation can be
considered.
Contact GE Fuji

Bring the ambient
condition to within
the specified limit.

No

Yes

No

No

Yes

Yes

No

No

Yes

No

Replace the cooling
fan(s).

Reduce the load or
increase the drive
capacity.

Advertising