LCD
GRAPHIC

FACTORY

FUNCTION

DISPLAY

SETTING

DESCRIPTION

SETTING

6-14

32 (cont'd)

X4 - function selected by 3rd digit:

- - 0 -

ACC/DEC time selection (two steps)

- - 1 -

Selects 4 to 20 mA as an input for
frequency reference at terminal (C1) (will ignore
speed pot, V1 inputs and keypad)

- - 2 -

DC brake command (can be used to maintain
stopped motor rotor position - see diagram and
notes)

NOTES:

– Strength of the dc brake is set by

Function Code 18.
Operation command takes precedence
(RUN, FWD, REV) (While X4 to CM is
ON, if FWD to CM is ON: dc brake reset.

– As dc current continues to flow to the

motor during the X4 to CM - ON period,
be careful of motor temperature rise. (When
long periods of dc braking are required
measure the motor's temperature continuously).

– DC brake time (Function Code 19) is ignored.

CAUTION: Motor may overheat if the dc brake is left ON for too long.

Output

Frequency

DC Brake

Frequency

DC Brake

FWD-CM

X4-CM

Advertising