GE Industrial Solutions AF-300E$ User Manual

Page 70

Advertising
background image

LCD
GRAPHIC

FACTORY

FUNCTION

DISPLAY

SETTING

DESCRIPTION

SETTING

6-13

30

MTR POLES

MOTOR POLES

4

The number of motor poles is set only for
the display of synchronous RPM. It has NO
effect on drive operation. Adjustable from
2 to 14 (even numbers only).

Example: When a 4 pole motor is operated at 60
Hz, the synchronous RPM display should read
60 x 120/4 = 1800 RPM.
Recall, synchronous speed (in RPM) = Hz x 120(Constant)
# poles

* 31

32-41

FUNCTION CODE BLOCK DISPLAY

0

This setting determines whether or not
Function Codes 32 through 41 will be displayed
and available for adjustment.

0:

Function Codes 32 through 41 NOT displayed.

1:

Function Codes 32 through 41 displayed.

INPUT TERMINAL FUNCTIONS

32

X1-X5 TERM

X1 THROUGH X5 TERMINAL FUNCTIONS

0000

This Function Code determines the functions
of the X1 through X5 contact inputs on the
terminal block. It is adjustable from 0000
to 2223. Each of the four digits has a
separate meaning as defined below.

X1 and X2 - function selected by 1st digit:

0 - - -

Multistep speed selection (four steps)

1 - - -

UP/DOWN control 1 (start from 0 Hz)

2 - - -

UP/DOWN control 2 (start from previous
setting).

X3 - function selected by 2nd digit:

- 0 - -

Multistep speed selection (8 steps using
X1, X2, and X3).

- 1 - -

Switching operation from line to drive
(50 Hz)

- 2 - -

Switching operation from line to drive
(60 Hz)

2 Poles

=

3600 RPM

4 Poles

=

1800 RPM

6 Poles

=

1200 RPM

8 Poles

=

900 RPM

10 Poles

=

720 RPM

12 Poles

=

600 RPM

14 Poles

=

514 RPM

Advertising