GE Industrial Solutions AF-300E$ User Manual

Page 16

Advertising
background image

3-1

Installation Environment
Install the drive in an indoor location that meets the following
requirements:

— The ambient temperature is between -10

°

C and +50

°

C

(+14

°

F to +122

°

F). (Remove the ventilation cover when

the temperature exceeds +40

°

C [+104

°

F].)

— The relative humidity is between 20% and 90%. Avoid

any location subject to condensation, freezing, or where
the drive would come in contact with water.

— Do not install in any location subject to direct sunlight,

dust, corrosive gas, inflammable gas, or oil mist.

— The drive should be installed at an elevation below

1000 meters (3281 feet). Installation above 1000
meters (3300 feet) will need to be derated 1% per 333
feet.

Example:

5 Hp, 460 VAC, output current 9 amps. Application
altitude 3900 feet.

% derate = x 1% = 1.8%

(9 amps) x

= 8.84 amps derated

output current.

Motor derate may also be required, contact motor

manufacturer.

— Vibration should be less than 0.6G.

Installation Mounting Clearance
CAUTION:

Because the ambient temperature greatly
affects drive life and reliability, do not install the drive in any
location that exceeds the allowable temperatures.

— Install at a sufficient distance from other equipment,

walls, or wiring ducts as shown in Figure 3-1 (these
clearances are required to allow the heat generated by
the drive to escape).

— Install the drive perpendicular to the ground and with

the lettering right side up. (If the drive is installed
upside-down or horizontally, heat build-up will occur.)

Section 3: Installation Guidelines

3900 - 3300

333

( )

100 - 1.8

100

( )

CAUTION:

The mounting wall for the drive must be constructed of
heat resistant material because during operation, the
temperature of the Inverter's cooling fins rises to approxi-
mately 90 degrees C (194

°

F).

NOTE: When installing two or more drives in close
proximity, allow sufficient space as shown in Figure 3-1 and
install them in a horizontal row. If they must be installed in
a vertical column, at least 19.7 inches (50cm) internal
space must be provided between each one or a ventilation
baffle should be provided to prevent the ambient tempera-
ture from rising.

— Mounting screws or bolts should be of appropriate size

for weight of drive.

— See the appropriate view in Figure 3-2 for the location

of mounting holes.

— After removing the knockouts in the wiring lead in

plate, install the rubber bushings supplied to prevent
cable damage and to minimize dust entry.

Figure 3-1. DRIVE MOUNTING CLEARANCE

2.0” (5 CM)
or more

4.8” (12CM) or more

4.8” (12CM) or more

2.0” (5 CM)
or more