GE Industrial Solutions AF-300E$ User Manual

Page 96

Advertising
background image

8-1

TABLE 11: Fault Condition Description and Operation

The following GE AF-300E$ drive protection functions have been incorporated in the basic drive software and will be
indicated in the LED display as well as listed in the fault table display.

Section 8: Troubleshooting

Protective

Function

Function Explanation

LED

Display

Remarks

Alarm RY

(30A, B & C)

Overcurrent

Protects the Drive when the output current reaches the
momentary overcurrent protection level.
The protection is effective for Drive output terminals- U, V, W.

O C 1
O C 2
O C 3

At accel
At decel
At oper

X

Ground Fault

Grounded output. The protecction is effective for Drive output
terminals - U, V, W.

EF

Grnd Fault

X

Over voltage

Protects the Drive when the DC bus voltage reaches the
momentary overvoltage protection level by a braking operation.
(Drive cannot protect against an input line overvoltage.)

O U 1
O U 2
O U 3

At accel
At decel
At oper

X

Under voltage

Protects the Drive when the DC bus voltage reaches the
momentary low voltage protection level. Output alarm relay
(30a, b & c) is dependent on function.

L U

Function
10: 0 or 1
10: 2,3,4

X

- no

Over heat

Protects the Drive against overheating caused by
overload operation, cooling fan failure, abnormal high ambient
temperatures, etc.

O H 1
O H 3

Fin temp.
Internal
temp.

X

DB (Dyn Brk)

Protects the dynamic brake resistor from over-heating

d b H

X

Electronic

thermal

overload

Protects the Drive with electronic overload.
Protects the motor with electronic overload sense
Range of setting: 20 to 135% of Drive rated current.

O L U
O L

X

Inside fuse

Detects the DC bus failed fuse, 15 Hp and above.

F U S

X

External

Stops Drive by an external alarm signal.

O H 2

X

Memory error

Detects memory EE-PROM malfunction.

E r 1

X

Keypad

communication

Detects a continuous communication error between
control PCB and keypad panel.

E r 2

X

CPU error

Detection of a CPU malfunction.

E r 3

X

Option

communication

Detects a continuous communication error between
control PCB and option PCB.

E r 4

X

Option error

Detects Drive option failure.

E r 5

X

Operating

Proc. Error

Detects Drive operating procedure error during Drive startup.
FWD or REV connected to terminal CM at time of main power
being applied to Drive. Stop keypad in remote operation.

E r 6

X

Tuning error

Detects missing connection to the motor @ auto-tune.

E r 7

X

Prevent

stall

Prevents OC-trip by ceasing frequency output at high current when
torque limit is disabled and drive is accelerating, or when high impact
loads are applied to the motor. Second, by decreasing frequency
level when torque limit is activated and its value is being exceeded
during steady state operation and load acceleration.

Advertising