GE Industrial Solutions AF-300E$ User Manual

Page 90

Advertising
background image

LCD
GRAPHIC

FACTORY

FUNCTION

DISPLAY

SETTING

DESCRIPTION

SETTING

6-33

* 85

RESET INT

RESET INTERVAL

5

Time interval between reset attempts as set
in Function Code 84.

2 TO 20

Time in seconds.

MOTOR CHARACTERISTICS

86

MOTOR CAP

MOTOR Hp CAPACITY

1

This Function Code is used to select the
motor Hp capacity in relation to the
drive Hp capacity.

0:

One frame up in Hp capacity (variable torque
application).

1:

Standard capacity (constant torque application).

2:

One frame down in Hp capacity.

3:

Two frames down in Hp capacity.

87

MOTOR 1-Ir 0.00 TO

MOTOR #1 NAMEPLATE FULL LOAD CURRENT

RATED

2000

AMPS

88

MOTOR 1-Io 0.00 TO

MOTOR #1 NO LOAD CURRENT (Magnitizing

2000

current).

89

MOTOR 2-Ir 0.00 TO

MOTOR #2 NAMEPLATE FULL LOAD CURRENT

RATED

2000

AMPS

90

TUNING

MOTOR TUNING

0

This Function Code is used to tune the
primary resistance and inductance of the
motor.

0:

Inactive

1:

Active

WARNING: Ensure the motor is connected, free to rotate and at a standstill. Upon setting

Function Code 90 equal to 1, the drive will pulse the motor three (3) times in order to calculate

the settings in Function Codes 91 and 92.

CAUTION: When using motor tuning, be sure the correct values are set in Function Code 03, 04 and 87.