Table 5: terminal identification/function – GE Industrial Solutions AF-300E$ User Manual

Page 39

Advertising
background image

4-8

Table 5:

Terminal Identification/Function

Terminal

Terminal

Label

Name

Function

POWER TERMINAL BOARD

L1, L2,

ac Supply Line

Connection for commercial power (200-230 VAC or 380-460 VAC);

L3

Input Terminals

3-phase; 50⁄60 Hz.

U, V, W

Drive Output

Connection for 3-phase induction motor.

Terminals

P+, DB

External Braking

Connection for external braking resistor.

Resistor Terminals

(Only on 10 Hp or less.)

N-, P+

External Braking

Connection for external braking resistor via external braking unit.

Unit Terminals

(Only required on 15 Hp)

P+, P1

DC Reactor

Connection for a dc link reactor on unit rated 100 Hp and greater.
These terminals are jumpered on units rated 75 Hp and less.

E (G)

Ground Terminal

Connection for ground. Note: Be sure to ground the chassis to
prevent electrical shock & to reduce radio noise.

RO, TO

Control Power

Connection point for single-phase, 460 ac power for backing up the

Auxiliary Input

control circuit power when input starter is used (40 Hp and greater.)

U1, U2

Auxiliary Transformer

Factory connection set at U1 for 400 - 460 VAC input.

Taps

Reconnect to U2 for 380 VAC input. (40 Hp and greater)

CONTROL TERMINAL BOARD

Frequency Setting

Common terminal for terminals 12, 13, C1 & V1, and FMA (Do not

11

Common Terminal

connect to CM terminal or electrical noise immunity may be lost.)

12

Frequency Setting

When 0 to +10 VDC (0 to 5V) is input, the maximum frequency is

Voltage Input

reached at +10 VDC (5V) and is proportional to output frequency
down to 0 VDC. Input impedance is 22K ohm. Must be isolated source.

13

Frequency Setting

Regulated +10 VDC power supply for frequency setting potentiometer,

Voltage Output Term.

10mA or less (13 to terminal 11.)

C1

Frequency Setting

When the input signal is +4 to +20mA dc, the maximum frequency is

Current Input

reached at 20mA and is proportional down to a minimum frequency
setting at 4mA. Input impedance is 250 ohm. Must be isolated source.

V1

Voltage Input

Reaches maximum output frequency at +/- 10 VDC (the output

Auxiliary Terminal

freq. is proportional down to 0 VDC.) Input impedance is 22K ohms.
Must be isolated source.

CM

Control Circuit

Common terminal for control input commands, and FMP pulse

Common Terminal

output signal. (Do not connect to terminal 11.)

FWD

Forward Command
Input Terminal

Forward command via FWD-CM (closed). Reverse command via
REV-CM (closed). When FWD-CM is closed and REV-CM is closed

Reverse Command

at the same time, the drive will decelerate to stop.

REV

Input Terminal

BX

Motor Coast-To-Stop

Motor will coast-to-stop with BX-CM (closed). (For use when

Input Terminal

applying mechanical brake with drive in operation.) Note: If
BX-CM is opened with FWD or REV closed, the drive will start
operating.