Frequency Setting Resolution

– Analog: 1⁄3000 of max. frequency (0.02 Hz/60 Hz; 0.04 Hz/120 Hz)
– Digital: 0.01 Hz (max. frequency up to 99.99 Hz);

0.1 Hz (max frequency of 100 Hz or more)

Accuracy (Stability)

– Analog setting:

±

0.2% of max. frequency (@ 25

±

10

°

C)

– Digital setting:

±

0.01% of max. frequency (@ -10 to + 50

°

C)

Voltage/Frequency

Voltage - 80-240 VAC, 320-480 VAC

Characteristics (V/F)

Frequency - 0.2 to 400 Hz

Torque Boost

– Auto: Automatic torque boost control by torque calculated value.
– Manual: 0.0 to 20.0 code setting (includes the energy savings pattern,

Function Code for variable torque load.)

Acceleration/Deceleration

0.2 to 3600 seconds (independent acceleration/deceleration)

Characteristics

4 selectable linear and non-linear "S" curve characteristic.

Internal Functions:

The quality of the sound produced by the motor can be changed to

Operating Sound Selection

reduce irritating noise.

Frequency Meter Adjustment

Scale calibration of externally connected analog meter (6.5-10.5 VDC) or pulse frequency
6 to 100 times output frequency.

Data Protection

Data lock is possible to ensure that the data codes are not changed.

Pattern Operation

Seven independent stages (frequency up to 400 Hz, duration up to 6,000 seconds each.
Configuration:
Single cycle
Repeat cycling
Single cycle with continuous 7th speed

Momentary Power

Five selections available. (Refer to Power Supply Specification.)

Loss Ride Thru

High/Low Limiter

Output frequency upper and lower range limit 0 to 400 Hz; 1 Hz step settings.

Bias

Magnitude of the zero offset can be set from 0 to 100% of maximum
frequency (1 Hz steps.)

Gain

Output frequency gain corresponding to the reference signal can be set
from 0 to 200% (0.1% steps.)

Programmable Jump Frequency

Three selectable frequencies can be set to avoid a mechanical resonant point. Width is
adjustable from 0 to 30 Hz (1 Hz steps.)

Slip Compensation Control

Maintains motor at constant speed with load fluctuations.
Adjustable from -9.9 Hz to +5.0 Hz.

Torque Limit Control

Output torque can be controlled within a range of 20% to 180% (1% steps.)

7 Step Preset Speed

7 programmable preset speeds selectable by 3 contact closures.

Momentary or Maintained

Selection between the maintained contact operation/stop command (2-wire operation) or

Contact Operation

the momentary contact (3-wire operation).

Terminal Function Change

Multi-Use terminals changed via Function Code settings.
X1 to X5 inputs; Y1 to Y5 outputs.

Line to Drive Transition Logic

Motor transfer function from the AC line to Drive operation.

Sensorless Vector Control

– Improves torque characteristics throughout speed range.
– Improves speed regulation.