GE Industrial Solutions AF-300E$ User Manual

Page 75

Advertising
background image

LCD
GRAPHIC

FACTORY

FUNCTION

DISPLAY

SETTING

DESCRIPTION

SETTING

6-18

* 46

FMA FUNC

FMA OUTPUT INDICATION

0

This Function Code selects the quantity
to be displayed via the analog output
between the FMA and II terminals.

0:

Output frequency (0 to 100% full scale)

1:

Output current (0 to 200% full scale)

2:

Output torque (0 to 200% full scale)

3:

Output power (0 to 200% full scale)

CAUTION: The load impedance placed between
the FMA and 11 terminals should be a minimum
of 10,000 OHMS.

OUTPUT TERMINALS

47

Y1-Y5 TERM

Y1-Y5 OPEN COLLECTOR OUTPUT TERMINALS

01234

This Function Code determines the functions
of the Y1-Y5 open collector outputs on the
terminal block. It is adjustable from 00000
to FFFFF. Each of the five digits can be set
to one of the following selections to configure
its corresponding output.

0:

Drive running (RUN), see Function Code 57.

1:

Frequency at reference (FAR), see Function
Code 48.

2:

Frequency level detection (FDT), see Func-
tion Codes 49 and 50.

3:

Overload early warning (OL), see Function
Code 51.

4:

Undervoltage detection (LU).

5:

Keypad operation mode.

6:

Torque limiting, see Function Codes 15 and 16.

7:

Drive stopped (STOP).

8:

Auto-restarting, see Function Code 10.

9:

Auto-resetting.

A:

Initializing restart timer, picks up when power returns.

B:

NOT USED.

C:

Time-up signal (TP) for pattern operation,
picks up when changing to a new stage.

D:

Cycle completion signal (TO) for pattern
operation, picks up at completion of stage 7,
see Function Code 65.

NOTE: Auto Restart, setting of A, requires two (2)

wire maintained contacts (see Pg. 4-14).
Auto Reset requires three (3) wire start/stop.
Auto restart and auto reset cannot be activated
at the same time.