GE Industrial Solutions AF-300E$ User Manual

Page 88

Advertising
background image

LCD
GRAPHIC

FACTORY

FUNCTION

DISPLAY

SETTING

DESCRIPTION

SETTING

6-31

73

ACC PTN

ACCELERATION/DECELERATION PATTERN

0

Selection can be made from the following
types:

0:

Linear acceleration/deceleration (Fig. a)

1:

S curve acceleration/deceleration (Fig. b)

2:

Non-linear for variable torque load (Fig. c)

74

N/A

NOT USED

0

75

ENERGY SAV

ENERGY SAVINGS

0

Automatically saves energy by weakening
the V/Hz pattern during light load opera-
tion.

0:

Inactive

1:

Active-Volt/Hz ratio is decreased auto-
matically at light loads. Not active
during acceleration or deceleration.

76

REV-PH LOC

REVERSE DIRECTION LOCK OUT

0

Prevents the drive from operating in
a reverse direction.

0:

Inactive

1:

Active-Will not allow the motor to run in
reverse direction even in pattern mode.

77

DATA INIT

DATA INITIALIZATION

0

Allows resetting Function Codes to factory
settings.

0:

Manual setting value (customized drive
settings).

1:

Return to factory default setting values.

* 78

LANGUAGE

LANGUAGE SELECTION

1

Allows selection of the language in which
the LCD Graphic Display will be shown.

0:

Japanese

1:

English

2:

Spanish

3:

French

SPECIAL FUNCTIONS

Accel

Decel

Output

Frequency

t

Linear

Accel

Decel

Output

Frequency

t

S Curve

Accel

Decel

Output

Frequency

t

Non-Linear

Fig. A

Fig. B

Fig. C

Advertising