4-3

Table 4: AF-300E$ Drive Cable Size Recommendations & Circuit Protection Rating

230V

DB UNIT &

INCOMING POWER

HP

CURRENT

POWER

DC LINK REACTOR

AC-LINE DEVICE

2

CONST

VAR

CONST

VAR

CABLE AMP

CABLE

AMP

CIRCUIT

TRQ

TRQ

TRQ

TRQ

AWG

QTY

TERMINAL #

AWG

1

QTY

TERMINAL #

FUSES

BREAKER

0.5

0.5

3

3

16

1

14

1

6

15

1

1

5

5

16

1

14

1

10

15

2

2

8

8

14

1

14

1

15

15

3

3

11

11

14

1

14

1

20

20

5

5

17

17

10

1

10

1

30

30

7.5

10*

25

29

8

1

8

1

60

50

10

15*

33

42

6

1

6

1

80

60

15

20*

46

55

4

1

4

1

100

75

20

25*

59

68

2

1

2

1

125

100

25

30*

74

80

1

1

2

1

150

125

30

87

1

1

1/0

1

150

150

460V

DB UNIT &

INCOMING POWER

HP

CURRENT

POWER

DC LINK REACTOR

AC-LINE DEVICE

2

CONST

VAR

CONST

VAR

CABLE

AMP

CABLE

AMP

CIRCUIT

TRQ

TRQ

TRQ

TRQ

AWG

QTY

TERMINAL #

AWG

1

QTY

TERMINAL #

FUSES

BREAKER

1

1

2.5

2.5

16

1

14

1

6

5

2

2

3.7

3.7

16

1

14

1

10

10

3

3

5.5

5.5

16

1

14

1

15

15

5

5

9

9

14

1

14

1

15

15

7.5

10 *

13

16.5

10

1

14

1

30

30

10

15 *

18

23

10

1

14

1

40

30

15

20 *

24

30

8

1

14

1

50

40

20

25 *

30

37

6

1

14

1

60

50

25

30 *

39

44

6

1

14

1

80

60

30

45

45

4

1

12

1

80

75

40 *

45

52

4

1

31812

12

1

321600

80

100

40

50 *

60

66

2

1

321600

12

1

321868

100

100

50

60 *

75

77

1/0

1

321868

10

1

31812

125

125

60

75 *

91

96

1/0

1

321868

8

1

321600

150

150

75

100 *

112

124

1/0

1

321868

6

1

321600

175

150

100

125 *

150

156

3/0

1

36927

6

1

321878

175

200

125

150 *

176

180

1/0

2

321868

6

1

321868

200

200

150

200 *

210

253

1/0

2

321868

4

1

36923

300

225

200

250 *

304

304

3/0

2

36929

4

2

171500-2

350

400

250

300 *

377

377

250

2

171500-2

4

2

171502-2

400

400

300

350 *

415

415

300

2

171500-2

4

2

171502-2

500

500

* In variable torque applications, Function Code 86 (Motor Hp Capacity) needs to be changed to Set Drive Hp vs. Load Hp.

40 Hp and above is 460-480 VAC input, VT applications only.
1 Device ratings such as system coordination, short-circuit rating and type must be carefully reviewed by the user.
2 Based on GE Fuji DB resistor designs. Other ratings require careful review.
3 Device ratings such as system coordination, short-circuit rating and type must be carefully reviewed by the user.
Note: Wire size from NEC table 310-16. Copper wire rated 60 Deg. C for 100 amps or less, 75 Deg. C for over 100 amps in 30 Deg. C
ambient and 1.25 times Drive rated amps. These are minimum wire sizes; consult and conform to local and national codes.

CAUTION: The grounding connector shall be sized in accordance with the NEC or Canadian Electrical Code. The connection shall be made
by a UL listed or CSA certified closed-loop terminal connector sized for the wire gauge involved. The connector is to be fixed using the
crimp tool specified by the connector manufacturer.
Recommend GE Spectra RMS MAG-BREAK Circuit Breakers.
CAUTION: Quick-acting bussman JKS or equivalent J-class AC line fuses are required on 30 Hp or lower Drives. Check local electrical codes
for 40 Hp and higher.