GE Industrial Solutions AF-300E$ User Manual

Page 59

Advertising
background image

LCD
GRAPHIC

FACTORY

FUNCTION

DISPLAY

SETTING

DESCRIPTION

SETTING

6-2

02

MAX Hz

MAXIMUM HERTZ

60

Maximum output frequency is adjustable from
50 Hz to 400 Hz in 1 Hz steps.

03

BASE Hz-1

BASE FREQUENCY #1

60

Base frequency for motor #1 is adjustable
from 30 Hz to 400 Hz in 1 Hz steps.
(30 to 120 Hz, 40 Hp & above, var. torque loads.)

04

RATED V-1

RATED VOLTAGE #1

230

Maximum output voltage for motor #1 is

(460)

adjustable from 80 to 240 VAC (230V
Drives), or 320 to 480 VAC (460V
Drives)

NOTE: On 30 Hp and lower when set at zero (0),

the maximum output voltage will follow the
AC line input. Function Code 29 setting
will affect this Function Code.

* 05

ACC TIME 1

ACCELERATION TIME #1

6.0

Acceleration time #1 is adjustable from (30HP and less)
0.01 to 3600 seconds. Note that this

20.0

setting defines the time to accelerate from (40HP and greater)
zero to maximum frequency (Function Code 02).
Smaller frequency steps will result in shorter
acceleration times because the rate is
constant.
Example: ACC TIME 1 = 10 seconds

MAX Hz = 60

The acceleration rate is 6 Hz/sec, therefore a
step from 8 to 42 Hz would take (42-8)/6 =
5.6 seconds.

* 06

DEC TIME 1

DECELERATION TIME #1

6.0

Deceleration time #1 is adjustable from (30HP and less)
0.01 to 3600 seconds. Rules are the same

20.0

as for Function Code 05 except that a (40HP and greater)
setting of zero (0) causes the motor to coast
down until it reaches the new set point.
(Available up to 30 HP only)

WARNING:

Review motor capabilities for operation above motors's base frequency.

WARNING:

Review motor capabilities for operation above motors's base frequency.

Maximum frequency