GE Industrial Solutions AF-300E$ User Manual

Page 91

Advertising
background image

LCD
GRAPHIC

FACTORY

FUNCTION

DISPLAY

SETTING

DESCRIPTION

SETTING

6-34

* 91

%R1 SET

MOTOR #1 CALCULATED % PER UNIT RESISTANCE

%

0.00 TO

Percent of motor resistance.

50.00 %:

%R1 = R1 + Cable R x 100
V/ (

3 x I)

R1 is motor resistance;
Cable R is resistance of cable between drive
and motor; V is rated motor voltage.

* 92

%X SET

MOTOR #1 CALCULATED % PER UNIT IMPEDANCE

%

0.00 TO

Percent of motor impedance.

50.00 %:

%X = X1 + X2 x XM/ (X2 + XM) + Cable X x 100
V/ (

3 x I)

X1, X2, XM are motor values;
Cable X is inductance of cable between drive
and motor; V is rated motor voltage.

93

DD FUNC 1

DO NOT USE

94

DD FUNC 2

DO NOT USE

95

DATA PRTC

DATA PROTECTION

0

Once the Function Codes have been set, the
data protection can be activated and prevent
any further changes.

0:

Not protected (changeable)

1:

Protected (change prevented)

Press >> and UP Key together to change Function
Code 95 to 1.
Press >> and DOWN Key together to change Function
Code 95 to 0.
Press FUNC DATA to store change in software.