GE Industrial Solutions AF-300E$ User Manual
Page 91
LCD
GRAPHIC
FACTORY
FUNCTION
DISPLAY
SETTING
DESCRIPTION
SETTING
6-34
* 91
%R1 SET
MOTOR #1 CALCULATED % PER UNIT RESISTANCE
%
0.00 TO
Percent of motor resistance.
50.00 %:
%R1 = R1 + Cable R x 100
V/ (
√
3 x I)
R1 is motor resistance;
Cable R is resistance of cable between drive
and motor; V is rated motor voltage.
* 92
%X SET
MOTOR #1 CALCULATED % PER UNIT IMPEDANCE
%
0.00 TO
Percent of motor impedance.
50.00 %:
%X = X1 + X2 x XM/ (X2 + XM) + Cable X x 100
V/ (
√
3 x I)
X1, X2, XM are motor values;
Cable X is inductance of cable between drive
and motor; V is rated motor voltage.
93
DD FUNC 1
DO NOT USE
94
DD FUNC 2
DO NOT USE
95
DATA PRTC
DATA PROTECTION
0
Once the Function Codes have been set, the
data protection can be activated and prevent
any further changes.
0:
Not protected (changeable)
1:
Protected (change prevented)
Press >> and UP Key together to change Function
Code 95 to 1.
Press >> and DOWN Key together to change Function
Code 95 to 0.
Press FUNC DATA to store change in software.
SPECIAL FUNCTIONS