NOTES:

– When X1 – CM, X2 – CM, and X3 –

CM are all OFF, frequency reference is
set by keypad (/\ \/ keys) or by the
analog inputs per Function Code 00 setting.

– A setting in Function Code 20 through 26

above the maximum frequency in Function
Code 02 is NOT possible.

– When Function Code 65 equals 1, 2, or 3,

pattern operation is active.

* 27

DBR OL

DYNAMIC BRAKING RESISTOR OVERLOAD

0

The drive has a pre-programmed electronic (15 Hp and UP)
thermal overload protection function for the

1

dynamic braking resistors for Drives rated (UP TO 10 Hp)
10 Hp and below. Drives rated 15 Hp and
above, or for non-standard braking resistor
packages, use a thermal overload sensing
device.

0:

Inactive (15 Hp and greater or non-standard
DB resistors)

1:

Active (for internal braking resistor, up to
10 Hp.

MULTI STEP FREQUENCIES (Cont'd)

Output

Frequency

X1-CM

X2-CM

X3-CM

FWD-CM

t

Analog

Digital

Speed

1

Speed

2

Speed

4

Speed

5

Speed

6

Speed

7

Speed

3