Environmental conditions, Output, Power supply – GE Industrial Solutions AF-300E$ User Manual

Page 8: Table 1: af-300e$ – standard specifications

Advertising
background image

2-3

Environmental Conditions

Enclosures

NEMA 1 Standard

Installation Location

Suitable for indoor mounting only, less than 1000 meters (3300 feet) elevation, not in
contact with corrosive gas, oil mist, dust, and out of direct sunlight.

Stored Temperature

-20

°

to +65

°

C (-4

°

to + 149

°

F)

Ambient Temperature

-10 to +50

o

C (+14 to +122

o

F) (remove ventilation covers if temperature is over +40

o

C

[+104

o

F] up to 30 Hp; 40 Hp and above not required.)

Humidity

20% to 90% relative humidity (non-condensing).

Vibration

0.6G or less.

Cooling Method

1/2 to 1 Hp – Convection

2 Hp and greater – Forced air

Output

Rated Output Voltage

3-Phase, 3-Wire Type, 80-240 VAC or 320-480 VAC
(Can not exceed power supply voltage).

Frequency Range

0 - 400 Hertz (0.2 to 60 Hz start frequency; 0.2 to 120 Hz base frequency).
Above 120 Hz, contact Company for approval of application.

Overload Current Rating

– 30 Hp and lower

150% for 1 minute duration (inverse time characteristic)
200% for 0.5 seconds

– 40 Hp and greater

150% for 1 minute duration (inverse time characteristic) 180% for 0.5 seconds

Power Supply

Rated Input AC Voltage

– 200 to 230 VAC 50/60 Hz, 3 phase (1/2 to 30 Hp)
– 380 to 400 VAC 50 Hz, 3 phase (1 to 300 Hp) CT
– 380 to 480 VAC 60 Hz, 3 phase (1 to 300 Hp) CT
– 460-480 VAC, 60 Hz, 3 phase, 40 Hp and above, variable torque applications only

Voltage - +10%, -15%; Voltage Unbalance - Within 3%; Frequency - +/-5% Units are
dual rated Constant Torque/Variable Torque. Drive looks for a similar Volts/Hz ratio).

Control System

Sinusoidal PWM Control (or with torque-vector control.)

Momentary Voltage Dip

When the input voltage dips below 165 VAC (230V System), 310 VAC (460V system) or
400 VAC (575V System), the Drive can operate for 15 ms with 85% full load applied.

Starting Torque

150% (when torque vector control is active.)

Carrier Frequency

– 2 to 15 KHz (1/2 to 30 Hp) 230 & 460 VAC
– 2 to 10 KHz (40 to 75 Hp) – 2 to 6 KHz (100 Hp and greater)

Table 1: AF-300E$ – Standard Specifications