GE Industrial Solutions AF-300E$ User Manual

Page 77

Advertising
background image

LCD
GRAPHIC

FACTORY

FUNCTION

DISPLAY

SETTING

DESCRIPTION

SETTING

6-20

OUTPUT TERMINAL FUNCTIONS

* 48

FAR HYSTR

FREQUENCY AT REFERENCE HYSTERESIS (WIDTH)

2.5

The signal is on when the output frequency
equals the frequency reference’s set point.
This is an open collector output and can be
used in conjuction with a relay unit to allow
connection to system control circuitry.
Adjustable from 0.0 to 10 Hz in 0.1 Hz steps.

* 49

FDT LEVEL

FREQUENCY DETECTION THRESHOLD

60

The signal is on when the output frequency
exceeds the detection level setting. This
is an open collector output and can be used
in conjuction with a relay unit to allow
connection to system control circuitry.
Adjustable from 0 to 400 Hz.

Far
Hyster

Far
Hyster

Far
Signal

t