background image

LCD
GRAPHIC

FACTORY

FUNCTION

DISPLAY

SETTING

DESCRIPTION

SETTING

6-17

FMA

11

Adjustment
Range

ANALOG MONITOR OUTPUT

* 43

FMP PULSES

FMP FREQUENCY PULSE OUTPUT

24

The FMP terminal provides a pulse whose
output is proportional to drive output
frequency. The number of pulses per
second is given as output Hz multiplied by
the setting in Function Code 43 with a
maximum output of 6,000 pulses per second.
Function Code 43 is adjustable from 6 to
100. The output frequency is accurate to
within

±

1 %. Ex: 60Hz, setting 24 – 60x24 = 1440 pulses.

* 44

FMP V-ADJ

FMP VOLTAGE ADJUST

100

The average voltage of the FMP terminal
pulsed output can be adjusted from approxi-
mately 5 to 12 VDC by changing Function Code
44 from 50 to 120, respectively. The voltage
will be accurate to

±

5%. The peak voltage

of the pulses will be approximately 15.6 VDC
regardless of this setting, only the average
output voltage is changed. Ex: V

avg.

= 12V x 100 setting = 10V

120

CAUTION: The minimum load impedance which should be
placed between the FMP and CM terminals is 5,000 ohms.

* 45

FMA V-ADJ

FMA VOLTAGE ADJUST

100

The FMA terminal provides a 0 to +10 VDC
analog output which can indicate output
frequency, current, torque, or power (see
Function Code 46). This Function Code can
be used to adjust the voltage output by a
factor of 0.65 to 2.00 (note that the max-
imum available output is 10.3 VDC).
Adjustable from 65 to 200% for 10.3VDC output.