GE Industrial Solutions AF-300E$ User Manual

Page 76

Advertising
background image

LCD
GRAPHIC

FACTORY

FUNCTION

DISPLAY

SETTING

DESCRIPTION

SETTING

6-19

47 (cont'd)

E

Stage number indication for Pattern Operation,
requires Y3, Y4, and Y5 outputs, set Function
Code 47 equal - - EEE.

F

Alarm indication in alarm trip mode,
requires Y2, Y3, Y4, and Y5 outputs, set
Function Code 47 equal - FFFF.

Stage

1
2

Y3

Off
Off

Y4

Off
On

Y5

On
Off

3
4

Off
On

On
Off

On
Off

5
6
7

On
On
On

Off
On
On

On
Off
On

Cause of trip

Terminal

Y2 (F)

Y3 (F)

Y4 (F)

Y5 (F)

0

Off

Off

Off

Off

1

OC1

Off

Off

Off

On

2

OC2

Off

Off

On

Off

3

OC3 and EF

Off

Off

On

On

4

OU1, OU2, OU3

Off

On

Off

Off

5

LU

Off

On

Off

On

6

OL

Off

On

On

Off

7

OLU

Off

On

On

On

8

OH1, OH3

On

Off

Off

Off

9

OH2, dbH

On

Off

Off

On

10

FUS

On

Off

On

Off

11

Er1, Er3

On

Off

On

On

12

Er2

On

On

Off

Off

13

Er4

On

On

Off

On

14

Er5

On

On

On

Off

15

Er6, Er7

On

On

On

On

Advertising